Automatic Voltage Regulator AVR R180 for TAL Generators
Part NO.:
R180
Specification:
Sensing input: 3-ph/2-ph - 220/230/240/380/400/415 volts for 50 Hz 3-ph/2-ph - 208/240/277/380/416/440/480 volts for 60 Hz
Voltage range high: 300V to 530V
Voltage range low: 180V to 310V
Droop: 1 and 5A AC in U phase
Droop range: 8% droop at 0.8 PF
PMG input power: Continuous: 240V RMS +10% Momentary 5 s: 240V RMS + 30 Up to 240 Hz
AREP+ input power: Continuous: 250V peak+10% Momentary 10 s: 350V peak +5% - Up to 75 Hz
Excitation current: 6A DC continuous 9A for 5 seconds (short-circuit operation)
Regulation: ± 0.5% at AVR sensing terminals
Maximum excitation limit: 6A DC (factory setting)
Maximum excitation limit delay: 30 sec. (factory setting)
Under frequency protection: 48.5 Hz/58.5 Hz for 50 Hz/60 Hz operation
Slope: 1.2X (120%) V/Hz
Remote potentiometer: 1 kOhm for ± 10% adjustment
Accessory Input: ± 4.5V DC for ±15%
Temperature range: -25oC to +70oC
Storage temperature range: -40oC to +80oC
Thermal drift: 0.5% for 20oC change
Fuse: FST 10A 250V
Applications:
For Leroy-Somer Alternators
R180 |
---|
Automatic Voltage Regulator AVR R180 for TAL Generators for sale on our website.
In addition to Automatic Voltage Regulator AVR R180, you can also buy other models or other parts of Excavators, Forklift, Aerial Work Platforms AWP and etc. on our website.
Right parts, guaranteed. If you find any defects, let us know within 60 days and we’ll take care of it. Check out our Warranty Policy for more details.
We ship fast so you can get on the road that much faster. Check out our Shipping Policy for more details.
We’re only happy if you’re happy. If you’re not entirely satisfied with your order, you may be entitled to a refund. Check out our Return Policy for more details.